17Operating and installation manual for VR 61 mixer module
Display
screen
Title display
screen
adjustable
operating values
(just display = A)
Remarks Unit Min.
value
Max.
value
Step width Preset
value
C11 HC2
parameters
Set-back
temperature
For the times between
the time windows you
can set a set-back
temperature.
If your expert technician
has set the frost
protection function, the
set-back temperature is
automatically 5 °C. There
will be no display as set-
back temperature
°C 5 30 1 15
Heating curve in accordance with the
diagram operating
instructions Chapter 4.7.3
if, in A2, for heating
circuit mode HC2 "Zone"
is selected (hydraulic
drawing 4) the value
from HC1 for the heating
curve is applicable
0,2 4 0,05-0,1 1,2
Minimum
temperature
Minimum feed
temeprature for HC2;
if, in A2, for heating
circuit mode HC2 "Zone"
is selected (hydraulic
drawing 4) the value
from HC1 for the
minimum temperature is
applicable
°C 15 90 1 15
Maximum
temperature
Maximum feed
temeprature for HC2;
does not appear if
"Zone" selected in
heating circuit mode HC2
in A2
(Hydraulic drawing 4)
°C 15 90 1 75
C15 Hot water
parameters
Storage tank
charging offset
In order to avoid short
heating up periods
(improved utilisation of
condensing technology);
appears only if in A3 for
relay output"LP"has
been selected
R15401 15
Charging pump
overrun
Only relevant if the
charging pump is directly
connected to the mixer
module VR 61 (hydraulic
drawing 2);
appears only if in A3 for
relay output"LP"has
been selected
Mins. 0 10 1 5
Parallel charging does not appear if
"Zone" selected in
heating circuit mode HC2
in A2
(Hydraulic drawing 4)
On, Off Off
C16 Hot water
parameters
Legionella
protection day
Weekday or block of
days; Storage tank
heated to 70 °C for one
hour
OFF, MO, TU,
WE, TH, FR,
SA, SU, MO-
SU
OFF
Start legionella
protection Time of
the day
0:00 24:00 0:10 4:00
Start-up 7
Table 7.2 Display screens in the level for the expert technician